Production and sale of electric cables Tinker Cavi Italian cosenza calabria


Go to content

PRODUCT

___________________________________________________________________PRODUCT

N07V-K

SECTION VOTES
mmq

APPROXIMATE DIAMETER WITH CONDUCTOR

INSULATION THICKNESS AVERAGE

EXTERNAL DIAMETER

APPROXIMATE WEIGHT
KG/KM

Electrical resistance at 20 ° C
MAXIMUM /KM

Production

1

1,3

0,7

3,2

14

19,5

1,5

1,5

0,7

3,5

19

13,3

2,5

1,9

0,8

4,2

30

7,98

4

2,5

0,8

4,8

45

4,95

6

3

0,8

6,3

63

3,3

Retailer

10

3,9

1

7,6

100

1,91

16

5

1

8,8

159

1,21

25

6,6

1,2

11

255

0,78

35

7,7

1,2

12,5

345

0,554

50

9,4

1,4

14,5

490

0,386

70

11

1,4

17

680

0,272

95

12,5

1,6

19

895

0,206

120

15,5

1,6

21

1200

0,161

150

16,5

1,8

23,5

1400

0,129

185

18,5

2

26

1800

0,106

240

21,5

2,2

29,5

2400

0,0801

           

Table UNEL IEC 35752
Insulated power cables polivinicloruro fire retardant contained a corrosive gas emissions.
Non-sheathed single core cables with flexible conductors.

Technical Data
Rated voltage Uo / U 450/750 V.
Test voltage: 2500 V. a.c.
Maximum temperature: 70 ° C.
Maximum short circuit temperature: 160 ° C.
Stranded Flexible red copper.
Polyvinyl chloride insulation for R2.
The compound meets the requirements of the "specification sheet of PVC insulating quality R2" under the CEI 20-11 regulations and pass tests with oils prescribed in CEI 20-22 / II and the gases emitted during prescribed burning
in IEC 20-37 Part I.

Identification
Imprinting insulation engraving
Available colors
From 1 to 2.5 sq. mm: Light Blue, White, Yellow / Green, Grey, Brown, Black, Red, Orange, Pink, Purple, Dark Blue.
4 to 16 sq. mm: Light blue, Yellow / Green, Grey, Brown, Black
From 25 to 95 sq. mm: Yellow / Green, Black
From 120 to 240 sq. mm: Black

Terms of use
Plants for which the CEI 64-2 cables provide the fire retardant. Facilities built or pipes within sight or within raceways.
Fixed or covered up or lighting fixtures, in cabinets or signaling and control. The cross section of 1 sq. mm is provided only for electric circuits of lifts and elevators or internal wiring of electrical signaling and control.

Pose
Minimum temperature: 5 ° C.
Maximum tractive effort: you should not exceed 50 N. per sq. mm of copper section.
Minimum bending radius: 4 times the outer diameter.

Package
In coils of 100 meters up to 50 mm ² section - Spools wood.


Back to content | Back to main menu